Chapter 2-6 RESIDENTIAL BUILDING CODES AND PERMITS
Section 2-6-2 RESIDENTIAL BUILDING CODE AMENDMENTS
All building construction work and the inspections thereof shall be in conformity with the provisions
of this Code and with the 2003 edition of the International Residential Code, with the exception of
Chapters 12-42 but with Appendices F, G, H, J and K which is hereby adopted by the City, with
the following specific deletions and additions:
Chapter 1 is deleted in its entirety and replaced to read as follows:
Unless any such code has been specifically adopted by the City, any reference to an (International
Code), including without limitation the following, shall be deemed to refer to the equivalent code,
if
any that has been adopted by the City:
ICC Electrical Code
International Energy Conservation Code
International Existing Building Code
International Fuel Gas Code
International Mechanical Code
ICC Performance Code
International Plumbing Code
International Private Sewer Disposal Code
International Administrative Code
International Urban-Wildland Interface Code
International Zoning Code
Equivalent adopted versions include the:
2002 National Electrical Code
2003 Uniform Mechanical Code
2003 Uniform Plumbing Code
1997 Uniform Administrative Code
1997 Uniform Code for the Abatement of Dangerous Buildings
Section R202 Definitions is amended by adding three new definitions to read as follows:
Sleeping Area. Any area that includes one or more sleeping rooms that
are located on the
same floor and are not separated by another habitable room, such as a living room, dining room,
or kitchen (but not a bathroom, hallway or closet).
Sleeping Room. Any bedroom or other room that is ordinarily used or intended
to be used for
sleeping purposes. The term is deemed to include any room that contains a closet and that
provides for occupant privacy.
Temporary. A defined time set by the Administrative Authority not to exceed
90 days.
Extension of time may be granted upon written request.
Subsection R301.1.2 Construction Systems is amended by adding a new paragraph to read as
follows:
All plan (unreinforced) concrete, plan (unreinforced) masonry and rubble stone
masonry
construction is prohibited. All tables, figures and references for these unreinforced systems
are
deleted.
Table R301.2(1) Climatic and Geographic Design Criteria is amended to read as follows:
TABLE
R301.2(1)
CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA
|
Ground
Snow
Load
|
Wind
Speed(e)
(mph)
|
SeismicDesign
Category
(g)
|
SUBJECT TO DAMAGE FROM
|
Decay
(d)
|
|
Weathering
(a)
|
Frost
Line
Depth(b)
|
Termite(c)
|
|
30#
|
90
|
D
|
Severe
|
30"
|
Slight to
Moderate
|
None
to
Slight
|
|
Winter
Design
(f)
|
Ice Shield
Under-Layment
Required (k)
|
Flood
Hazard
(sh)
|
Air
Freezing
Index (j)
|
Mean
Annual
Temp
(k)
|
|
-2
|
Yes
|
July 23,
1996
|
1500
|
45.9F
|
For SI: 1 pound per square foot = 0.0479kN/m2, 1 mile per hour = 1.609km/h.
(a) Weathering may require a higher strength concrete or grade of masonry than
necessary to
satisfy the structural requirements of this code. The weathering column shall be filled in with
the
weathering index (i.e., "negligible," "moderate" or "severe") for concrete
as determined from the
Weathering Probability Map (Figure R301.2(3)). The grade of masonry units shall be determined
from ASTM C 34, C 55, C 62, C73, C 90, C 129, C 145, C 216 or C 652.
(b) The frost line depth may require deeper footings than indicated in Figure
R403.1(1). The
jurisdiction shall fill in the depth column with the minimum depth of footing below finish grade.
(c) The jurisdiction shall fill in this part of the table with "very heavy,"
"moderate to heavy,"
"slight to moderate" or "none to slight" in accordance with Figure R301.2(6) depending
on whether
there has been a history of local damage.
(d) The jurisdiction shall fill in this part of the table with "moderate
to severe," "slight to
moderate" or "none to slight" in accordance with Figure R301.2(7) depending on whether
there
has been a history of local damage.
(e) The jurisdiction shall fill in this part of the table with wind speed from
the basic wind speed
map (Figure R301.2(4)). Wind exposure category shall be determined on a site-specific basis in
accordance with Section R301.2.1.4.
(f) The outdoor design dry-bulb temperature shall be selected from the columns
of 97 1/2 -percent values for winter from Appendix D of the International Plumbing Code. Deviations
from
the Appendix D temperatures shall be permitted to reflect local climates or local weather
experience as determined by the building official.
(g) The jurisdiction shall fill in this part of the table with the Seismic Design
Category determined
from Section R301.2.2.1.
(h) The jurisdiction shall fill in this part of the table with (a) the date of
the jurisdiction's entry into
the National Flood Insurance Program (date of adoption of the first code or ordinance for
management of flood hazard areas), (b) the date(s) of currently effective FIRM and FBFM, or
other flood hazard map adopted by the community, as may be amended.
(i) In accordance with Sections R905.1.7.1, R905.4.3, R905.5.3, R905.6.3, R905.7.3
and
R905.8.3, for areas where the average daily temperature in January is 25 degrees F (-4 degrees
C) or less, or where there has been a history of local damage from the effects of ice damming, the
jurisdiction shall fill in this part of the table with "YES."
(j) The jurisdiction shall fill in this part of the table with the 100-year return
period air freezing
index (BF-days) from Figure R403.3(2) or from the 100-year (99%) value on the National Climatic
Data Center data table "Air Freezing Index-USA Method (Base 32 degrees F)" at
www.ncdc.noaa.gov/fpsf.html.
(k) The jurisdiction shall fill in this part of the table with the mean annual
temperature from the
National Climatic Data Center data table "Air Freezing Index-USA Method (Base 32 degrees F)"
at
www.ncdc.noaa.gov/fpsf.html.
Figure R307.2 Minimum fixture clearances is deleted in its entirety without replacement.
Figure R403.1(1) Concrete and Masonry Foundation Details is amended to delete each reference
to 3.5 inches as the minimum slab thickness and replace it with a 4.0 inch minimum slab
thickness.
Subsection R403.1.1 Minimum Size is amended to read as follows:
R403.1.1 Minimum size. Minimum sizes for concrete and masonry footings shall
be set forth in
Table 403.1 and Figure R403.1(1). The footing width, W, shall be based on the load-bearing
value of the soil in accordance with Table R401.4.1. Spread footings shall be at least 8 inches
(203 mm) in thickness. Footing projections, P, shall be at least 2 inches (51 mm) and shall not
exceed the thickness of the footing. The size of footings supporting piers and columns shall be
based on the tributary load and allowable soil pressure in accordance with Table R401.4.1.
Footings for wood foundations shall be in accordance with the details set forth in Section R403.2,
and Figures R403.1(2) and R403.1(3).
Subsection R404.1.1 Concrete and Masonry Foundation Walls is amended to read as follows:
R404.1.1 Concrete and masonry foundation walls. Concrete masonry and clay masonry
foundation walls shall be constructed as set forth in Tables R404.1.1(2), R404.1.1(3) and
R404.1.1(4) and shall also comply with the provisions of this section and the applicable provisions
of Section R606, R607and R608. In Seismic Design Categories D1 and D2, concrete
masonry
and clay masonry foundation walls shall comply with Section R404.1.4. Rubble stone masonry
foundation walls shall be constructed in accordance with Sections R404.1.8 and R606.2.2. Rubble
stone masonry walls shall not be used in Seismic Design Categories D1 and D2.
Subsection R404.1.2 Concrete Foundation Walls is amended to read as follows:
R404.1.2 Concrete foundation walls. Concrete foundation walls shall be constructed
as set forth
in Tables R404.1.1(2), R404.1.1(3) and R404.1.1(4), and shall also comply with the provisions of
this section and the applicable provisions of Section R402.2. In Seismic Design Categories D1
and D2, concrete foundation walls shall comply with Section R404.1.4.
Subsection R404.1.4 Seismic Design Categories D1 and D2is amended to delete in
its entirety the
second paragraph (following Items 1 through 5) and to replace it with a paragraph to read as
follows:
Vertical reinforcement for masonry stem walls shall be tied to the horizontal
reinforcement in
the footings. Masonry stem walls located in Seismic Design Categories D1 and D2
shall have a
minimum vertical reinforcement of one No. 4 bar located a maximum of 4 feet (1220 mm) on
center in grouted cells.
Subsection R502.6.2 Joist Framing is amended to read as follows:
R502.6.2 Joist framing. Approved framing anchors shall support joists
framed into the side of a
wood girder.
Section R502.10 Framing of Openings is amended to read as follows:
R502.10 Framing of openings. Openings in floor framing shall be framed with
a header and
trimmer joists. When the header joist span does not exceed 4 feet (1219mm), the header joist
may be a single member the same size as the floor joist. Single trimmer joists may be used to
carry a single header joist that is located within 3 feet (914mm) of the trimmer joist bearing. When
the header joist span exceeds 4 feet (1210mm), the trimmer joists and header joist shall be
doubled and of sufficient cross section to support the floor joists framing into the header.
Approved hangers shall be used for the header joist to trimmer joist connections when the header
joist exceeds 6 feet (1829 mm). Tail joists over 12 feet (3658mm) long shall be supported at the
header by framing anchors.
Figure R606.10(3) Requirements for Reinforced Masonry Construction in Seismic Design
Category D1 and D2.is amended to read as follows:
The thickness of the footings as shown in this figure is 6 inches. The
thickness of the footing
shown in the "Foundation for wood floor" detail and the "Foundation for concrete floor"
detail is
amended from 6 inches (152mm) to 8 inches (203mm).
Detail "A" shall be amended to reflect that the Dowel and Rod detail
are not 3/8 inch, but shall
be a #4 reinforcing bar in accordance with Table R606.11.3.2.
Section R1007 Fireplace Requirement is added to read as follows:
R1007 Fireplace requirements. A gas or wood-burning fireplace installed
within a dwelling unit
shall comply with the following requirements:
1. The fireplace opening shall be provided with solid doors such as glass,
solid steel or cast
iron.
2. If the fireplace is located in a sleeping room or an adjacent bathroom,
then a permanent
unobstructed fresh air supply shall be provided directly from the exterior of the structure to the
firebox.
3. When gas is piped to the fireplace, a caution sign shall be installed
that states "Caution:
Damper must be permanently blocked open if gas is supplied to this fireplace." The letters
on the
sign must be a minimum of 3/8 inches in height.
Section AG105.2 Outdoor Swimming Pools Item 1 is amended to read as follows:
1. The top of the barrier shall be at least 5 feet (1524mm) above grade
measured on the side
of the barrier which faces away from the swimming pool. The maximum vertical clearance
between grade and the bottom of the barrier shall be 2 inches (51mm) measured on the side of
the barrier which faces away from the swimming pool. Where the top of the pool structure is
above grade, such as an aboveground pool, the barrier may be at ground level, such as the pool
structure, or mounted on top of the pool structure. Where the barrier is mounted on the top of
the
pool structure, the maximum vertical clearance between the top of the pool structure and the
bottom of the barrier shall be 4 inches (102m).
(Ord. 635, Amended, 08/23/2005, Prior Text; AB11, Amended, 09/25/2001, Effec 10-1-01:BOS to City Council, Prior Text; Res. 10-00, Amended, 05/23/2000, Adopted/Effective; 05-23-00 adopt 1997 Uniform Building Code, Prior Text; Res. 09-97, Amended, 03/25/1997, Effective/Adopted; 03-25-97, adopt uniform building code amendments, Prior Text; Res. 10-86, Amended, 06/10/1986, Adopted/Effective; 06-10-86, adopting uniform building code, Prior Text; Res. 03-80, Amended, 02/12/1980, Adopted/Effective; 02-12-80, adopted 1979 uniform building code, Prior Text)